This article provides step-by-step instructions for performing custom serial controller configurations on Elo touch controllers, altering touch data formats, and verifying output streams using legacy diagnostics.
⚠️ IMPORTANT - DEVELOPMENT INFORMATION ONLY
This information is intended as development reference for use by trained professionals and is not a standard procedure or statement of work. Elo/Zebra does not warrant or support this custom configuration and cannot be held liable for accidental or intentional misuse. Use this information at your own risk.
Sending SmartSet Commands to Alter the Touch Data Format
Modern Elo controllers can be programmed via a serial connection to a PC's RS232 interface (COM port) by sending simple alphanumeric ASCII command strings. Sending these commands allows you to change the touch data format or reverse one or both touch axes. You can use HyperTerminal (or a similar Windows serial communications utility) to transmit these commands.
A package of ASCII text command files is available to perform setup, older data format emulations, and other common changes. Commands must be sent one at a time.
💡 Critical Step: Save to NVRAM
You must send the Save_to_NVRAM command after all other setup commands have been transmitted. Sending configuration commands changes the temporary running state of the controller, but changes are only written to non-volatile memory when the Save command is executed. Failure to send this command will cause all changes to be lost when power is removed!
Limitations and Requirements
- Supported Controllers: This document applies only to Elo AccuTouch, IntelliTouch, and Surface Capacitive SmartSet touch controllers featuring a physical serial interface.
- Baud Rate Restriction: The 2216, 2700, 2701, and 5020 controllers run at 9600 baud ONLY. This baud rate cannot be altered.
- Driver Coexistence: HyperTerminal requires exclusive control of the COM port. The Elo Windows driver must be removed or disabled before attempting to send commands to release the port resources.
- To remove the Elo driver:
- Open the Windows Control Panel.
- Double-click Add or Remove Programs.
- Locate the Elo driver in the list (older legacy versions may be listed as Monitormouse), double-click it, click Remove, and confirm any prompts.
- To disable the driver: Alternatively, disable the driver in Device Manager under Mice and Other Pointing Devices by selecting "Do not use this device...". Note: You must manually re-enable this device later once setup is complete.
- To remove the Elo driver:
- Driver Compatibility Warning: Controllers configured to emulate legacy, non-SmartSet data formats will no longer communicate with native Elo Windows drivers, as standard drivers require the default SmartSet protocol.
- Physical Cabling: Ensure the touchmonitor's serial (9-pin female) output is connected directly to the PC's serial COM port (9-pin male). Ensure you know the correct COM port assignment before proceeding.
Altering the Touch Data Format: Step-by-Step Procedure
Note: If you are unfamiliar with Windows COM port configuration or basic command-line navigation, please coordinate with an IT administrator or system engineer.
- Download the attached utility archive: touchcontrollers_commands.zip.
- Extract (unzip) the file to a known folder on your local PC.
- To identify which command files to utilize, refer to the Identifying Data Formats section below.
- Launch HyperTerminal:
- Navigate to: Start > All Programs > Accessories > Communications > HyperTerminal.
- In the New Connection window, enter "Elo" (or your preferred configuration name) and click OK.
- Tip: If you have already saved an Elo HyperTerminal session, click Cancel, select File > Open, and double-click your existing configuration. This bypasses the port setup steps below.
- Configure the connection interface:
- In the "Connect using" drop-down menu, select the active COM Port associated with the controller, then click OK.
- In the Port Settings dialog, select 9600 from the Bits per second drop-down, then click OK.
- Transmit the command files:
- In the active HyperTerminal window, click Transfer in the top menu bar, then click Send Text File (ensure you select "Send Text File..." and not standard "Send File...").
- Navigate to the folder containing your unzipped command text files and double-click the target command file to send.
- A short, cryptic character string should display at the top of the terminal screen. This confirms a successful command echo back from the Elo controller.
- Troubleshooting: If no characters appear, the command was not sent. Verify cabling, COM configuration, and controller power.
- Repeat step 5 for any additional configurations. Note: Depending on system behavior, it may occasionally be necessary to restart the HyperTerminal session between files.
- Send the Save command file last to write your changes permanently to the controller's NVRAM.
Identifying Data Formats and Operating Modes
To view your live serial touch data stream, use the comdump.exe utility (available on the official Driver and File Downloads support page). Reviewing the data structure helps identify existing legacy formats to determine which emulation commands to deploy on modern hardware, or to verify if a recently configured controller is outputting the correct format.
Important Usage Notes:
- OS Environment:
comdump.exeis a legacy DOS application that must be executed from a command line prompt. Due to directory mapping, savecomdump.exedirectly to the root of your primary drive (e.g.,C:\comdump.exe) rather than nested folders. - Port Conflicts: The targeted COM port must be fully released. Ensure the native Elo driver is removed or disabled and close/disconnect active HyperTerminal sessions before executing.
- Port Limitations:
comdump.exesupports either COM1 or COM2 only.
If running HyperTerminal, click the Disconnect icon (phone receiver off the hook) to free the port for
comdump. When finished, press Esc in your Command Prompt to terminate comdump, press Alt+Tab back to HyperTerminal, and select Send Text File. The terminal will reconnect automatically.Running the Diagnostic Tool (comdump.exe):
- Open a Command Prompt: Start > All Programs > Accessories > Command Prompt.
Navigate to the root directory by typing:
cd\
and hitting Enter (ensure you use the backslash key above the Enter key). The prompt should display as
C:\>.- Initialize the utility:
- For COM1: Type
comdump 1and press Enter. - For COM2: Type
comdump 2and press Enter.
- For COM1: Type
- When you touch the screen, active packets will scroll in the data area. Look for the repeating hex sequences detailed below to verify your controller type:
| Data Format | Packet Characteristics | Description |
|---|---|---|
| SmartSet Binary | First two bytes are always [55] [54]; repeats every 10 bytes. | Distinctive modern native Elo data format. |
| 4002 Binary | Repeats every 6 bytes. | Legacy early 1990s protocol format. |
| 140 Binary | Repeats every 4 bytes. | Legacy 1980s protocol format. |
If the active byte values do not align with 10, 6, or 4-byte structures, press the M key on your keyboard to toggle the program output to ASCII Display Mode, touch the screen, and evaluate against these profiles:
- SmartSet ASCII: 16 bytes (if viewed in hex format). Displays 3 columns of 4-digit coordinates. The third column (representing pressure/status) never exceeds 255.
- 4002 ASCII: 16 bytes (if viewed in hex format). Displays 3 columns of 4-digit coordinates. The third column never exceeds 15.
- 140 ASCII: 11 bytes (if viewed in hex format). Displays 2 columns of 4-digit coordinates.
- 140 ASCII (with Touch Flags): 13 bytes (if viewed in hex format). Displays 2 columns of 4-digit coordinates plus 1 column displaying
T(Touch) orU(Untouch).
Troubleshooting Note: Data streams that fail to display or do not resemble any of the above patterns generally indicate the presence of a non-Elo touch controller interface.